ABB RER601 Technical Manual page 71

Wireless gateway
Hide thumbs Also See for RER601:
Table of Contents

Advertisement

1MRS757105 B
RER601/603
Technical Manual
Description
Serial Ports
Table 50:
Electromagnetic compatibility tests
Description
Electrostatic discharge test:
Contact discharge
Indirect contact discharge
Conducted RF Immunity test:
150 kHz...80 MHz
Table continues on next page
Value
Serial 1 / Console
Serial 2 / IEC 60870-5-101
Type test value
4 kV
4 kV
10 V (rms)
Section 7
Technical data
RS-232 DTE
Male DB-9 connector
IEC 60870-5-101 protocol
support
Full serial and modem
signals
300...460 800 bps.
Data bits – 7 or 8
Stop bits - 1 or 2
Parity - None, Even, Odd
Flow control – None, RTS/
CTS
Protection – 15 kV ESD and
short circuit
Console – RS-232, 19200
bps, 8 data bits, 1 stop bit,
no parity (8N1)
RS-232 DTE, RS-422,
RS-485 (selectable)
Male DB-9 connector
Full serial and modem
signals
Biasing and termination
selectable
300...460 800 bps
Data bits - 7 or 8
Stop bits - 1 or 2
Parity - None, Even, Odd
Flow control – None, RTS/
CTS
Protection – 15 kV ESD and
short circuit
IEC 60870-5-101 protocol
support
Reference
EN 61000-4-2
EN 61000-4-6