Communication Objects General - ABB i-bus KNX Product Manual

Valve drive actuator vaa/s x.230.2.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.2

Communication objects General

These communication objects are only available once per device and serve the interdisciplinary
(interoperable) functions.
No.
0
This communication object is enabled if in
"In operation" is set with the option yes.
In order to regularly monitor the presence of the device on the KNX, an in operation monitoring telegram can be sent
cyclically on the bus.
As long as the communication object is activated, it sends a programmable in operation telegram.
1
The communication object is enabled, if in
object "Request status values" 1 bit is parameterized with the option yes.
If a telegram with the value x (x = 0/1/0 or 1) is received on the communication object, all status communication objects are
sent on the bus, as long as these have not been programmed with the option after a change or request.
The following function results for the option x = 1:
Telegram value:
2
This communication object is enabled, if in
communication object: "Status man. operation" 1 bit has been parameterized with the option yes.
Telegram value:
The status of manual operation is sent after a change, after request or after a change and request as programmed.
3
This communication object is enabled if in
has been programmed with the option disable/enable via communication object.
Manual operation of the device is blocked or enabled via this communication object.
Using the value 0, the button
KNX operation occurs.
Using the value 1, the button
Telegram value:
Function
In operation
Parameter window
Request status values
Parameter window
1 = all status messages, provided they are programmed with the option after a change or request,
are sent.
0 = no reaction.
Status manual operation
Parameter window Manual
0 = manual operation not active
1 = manual operation active
Disable/enable man. operation
Parameter window Manual
is blocked on the device. If the device is in manual operation mode, immediate switchover to
is enabled on the device.
0 = button
enabled
1 = button
disabled
Object name
General
General, page 24, the parameter Send communication object
General
General, page 24, the parameter Enable communication
General
operation, page 26, the parameter Enable
General
operation, page 26, the parameter Manual operation
VAA/S x.230.2.1 | 2CDC 508 101 D0201 41
Data type
Flags
1 bit
C, R, T
DPT 1.002
1 bit
C, W, T
DPT 1.017
1 byte
C, R, T
DPT 1.011
1 bit
C, R, W
DPT 1.003