Communication Objects General - ABB i-bus KNX Product Manual

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.2

Communication objects General

No.
0
This communication object is enabled if in parameter window
object "In operation" is set with the option yes:
In order to regularly monitor the presence of the DLR/A on the KNX, a monitoring telegram can be sent cyclically on the
KNX.
1
Communication object is not assigned
2
The communication object is enabled if in
selected via the parameter Enable automatic DALI addressing with the option no.
Using this communication object, the internal function of the DLR/A is recalled, the DALI device addressing is verified and a
DALI address assigned if necessary.
Telegram value:
When the address assignment is recalled, the DLR/A verifies the DALI addresses. DALI devices without address receive a
DALI address. Doubled DALI addresses are separated.
120 2CDC507128D0202 | DLR/A 4.8.1.1
Function
In operation
empty
Trigger DALI addressing
Parameter window
0 = DALI address assignment not initiated
1 = DALI address assignment is recalled once
Object name
General
Parameter window
General, page 40, the parameter Send
General
General, page 40, the automatic address assignment is
Data type
Flags
1 bit
C, T
DPT 1.002
1 bit
C, W
DPT 1.003