Group objects General

No.
1
This group object is enabled if the Yes option has been selected for the Enable group object "In operation", 1 bit parameter
in the General parameter window.
To monitor regularly the presence of the device on the KNX bus, an In operation telegram is sent cyclically on the bus.
As long as the group object is activated, it sends a parameterizable In operation telegram.
The telegram value depends on the option selected in the Send parameter.
3
This group object is always enabled.
When this group object receives a telegram with the value 0 or 1, all Status group objects are sent on the bus if they were
parametrized with the On request option.
4
The group object is enabled if the Manual operation parameter is set to Enabled in the Manual operation parameter window.
This group object indicates whether manual operation is activated on the device.
Only the variant VC/S 4.2.1 has manual operation
5
The group object is enabled if the Manual operation parameter is set to Enabled in the Manual operation parameter window.
This group object activates or deactivates manual operation.
If the device is in manual operation, manual operation is deactivated again as soon as the value 0 is received.
Only the variant VC/S 4.2.1 has manual operation
Object function
In operation
Request status values
Status Manual operation
Note
Enable/disable manual operation
Note
Name
General
General
General
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 199
Data type
Flags
1 bit
C, R, T
DPT 1.002
1 bit
C, W
DPT 1.017
1 bit
C, R, T
DPT 1.011