ABB i-bus KNX Product Manual page 240

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Appendix
12.4.1.1.2
Calculation
With pulse width modulation, control is implemented by a variable mark-space ratio.
Fig. 30: Calculation
During the time t
On account of t
continuous control.
238 2CDC508220D0211 Rev. A | VC/S 4.x.1
the valve is opened and during the time t
ON
= 0.4 x t
the valve is set to about 40 %. t
CYC
ON
it is closed.
OFF
is the so-called PWM cycle time for
CYC