Group objects Channel A – Valve A
No.
17
This group object is always enabled and indicates the current device state. It indicates whether the device is working normally
or whether manual override is in effect.
This group object maps the following information:
•
Bit 0: Operating mode overridden
The controller was overridden via the Operating mode override group object.
This bit is always 0 in actuator mode.
0: No override
- 1: Override active
•
Bit 1: Building Protection
The device is in Building Protection mode due to dew point/fill level alarm or an open window
This bit is always 0 in actuator mode.
- 0: Building Protection
- 1: Building Protection active
•
Bit 2: Forced operation
Forced operation has been activated.
- 0: Forced operation inactive
- 1: Forced operation active
•
Bit 3: Manual override
The valve has been overridden manually via a group object.
- 0: Manual override inactive
- 1: Manual override active
•
Bit 4: Direct operation/membrane keypad
Manual operation via the device's membrane keypad is active
This option is available only for devices with membrane keypad
– 0: Manual operation inactive
– 1: Manual operation active
•
Bit 5: Security Mode
The device is in the Security mode, e.g. due to temperature value or control value failure, a predefined control value
(Cyclical monitoring parameter, page
When in controller mode, the device is also in Security Mode after booting up, because the controller has not yet received
a valid temperature value.
This does not depend on whether cyclic monitoring was activated for the temperature.
The device is operating normally when the group object value is 0 (= all individual bits = 0).
202 2CDC508220D0211 Rev. A | VC/S 4.x.1
Object function
Status byte channel
Note
Name
Channel A – General
145) applies.
Data type
Flags
1 byte
C, R, T
Non DPT