Open/Close Signal - ABB i-bus KNX Product Manual

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.9.1.2

Open/close signal

7.9.1.2.1
Dependent parameter
Valve drive operating principle, de-energized
This parameter is visible if, in the Valve output parameter, the Thermoelectric (PWM) or Open/Close signal
option has been selected.
Options:
This parameter determines the function of the valve drive.
Closed: If no current flows in the valve drive, the valve is closed. If current flows in the valve drive,
the valve opens.
Open: If no current flows in the valve drive, the valve opens. If current flows in the valve drive,
the valve then closes.
7.9.1.2.2
Dependent parameter
Open if control value greater than or equal to
Options:
The output switches ON continuously if the value parameterized here is greater than or equal to the
received control value. If a control value less than the parameterized value is received, the output switches
OFF.
Closed
Open
1...100 %
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 157