Enable Group Object "In Operation", 1 Bit - ABB i-bus KNX Product Manual

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.2.3.2
Dependent parameter
In period
Options:
This parameter defines the number of telegrams sent by the device within a certain period of time.
The telegrams are sent as quickly as possible at the start of a period.
The device counts the number of telegrams sent within the parametrized period. As soon as the
maximum number of sent telegrams is reached, no further telegrams are sent on the KNX bus until the
end of the period. A new period commences at the end of the previous period. The telegram counter is
reset to zero, and sending of telegrams is allowed again. The current group object value at the time of
sending is always sent.
The first period (break time) is not precisely predefined. It can be anywhere between zero seconds and
the parametrized time. The subsequent sending times correspond with the parametrized time.
Example:
Maximum number of sent telegrams = 5, period = 5 s. 20 telegrams are ready to send. The device
immediately sends 5 telegrams. The next 5 telegrams are sent after a maximum of 5 seconds. From this
point, a further 5 telegrams are sent on the KNX every 5 seconds. The telegrams are sent in the order
in which they arise (first in - first out).
7.2.4

Enable group object "In operation", 1 bit

Options:
yes: The group object is enabled.
no: The group object is not enabled.
1 second
2 seconds
5 seconds
10 seconds
30 seconds
1 minute
Note
No
Yes
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 41

Advertisement

Table of Contents
loading