ABB i-bus KNX Product Manual page 49

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.4.1.1
Dependent parameter
Basic-stage heating
The following description applies in the case that the Controller channel option has been selected in the
Channel function parameter.
Options:
The type of application for the heating stage is selected with this parameter. The controller is pre-
configured based on this selection and can be used for the selected application.
Deactivated: The heating stage is deactivated by selecting this option. All dependent parameters and
parameter windows are also deactivated.
Convector (e.g. radiator): This option should be selected if a convector, e.g. a radiator, is used as the
heating stage.
The Basic-stage heating control value type parameter is pre-parameterized to PI continuous
(0...100%) with the corresponding P and I proportions.
Area heating (e.g. floor): This option should be selected if an area, e.g. floor heating, is used as the
heating stage.
The Basic-stage heating control value type parameter is pre-parameterized to PI continuous
(0...100%) with the corresponding P and I proportions.
Free configuration: With this option it is possible to select freely the type of heating stage and also the
type of control. This option can be selected if the type of application is not entirely clear or if specific
adjustments are necessary.
The Basic-stage heating control value type parameter is pre-configured to PI continuous (0...100 %),
however it is possible to select freely between all control types.
Dependent parameters:
Additional-stage heating
Type of heating/cooling system
Heating/cooling changeover
Actuate basic-stage heating via
Deactivated
Convector (e.g. radiator)
Area heating (e.g. floor)
Free configuration
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 47