ABB i-bus
KNX
Parameters
7.7.4.2

Selection of Relative

7.7.4.2.1
Dependent parameter
Standby heating reduction
This parameter is only visible if the device has been parameterized for heating and the Deactivated option
has not been selected for the Basic-stage heating parameter in the Application parameters parameter
window, and the Setpoint specification and adjustment parameter has been parameterized with the
Relative option.
Options:
This parameter is used to set the temperature that is to apply in the Standby operating mode in the type of
operation cooling. This is defined here as the reduction in relation to the Comfort heating setpoint.
The controller does not change the type of operation to reach this temperature, instead it ensures this
temperature is not exceeded on an increase in the actual temperature.
7.7.4.2.2
Dependent parameter
Economy heating reduction
This parameter is only visible if the device has been parameterized for heating and the Deactivated option
has not been selected for the Basic-stage heating parameter in the Application parameters parameter
window, and the Setpoint specification and adjustment parameter has been parameterized with the
Relative option.
Options:
This parameter is used to set the temperature that is to apply in the Economy operating mode in the type
of operation cooling. This is defined here as the reduction in relation to the Comfort heating setpoint.
The controller does not change the type of operation to reach this temperature, instead it ensures this
temperature is not exceeded on an increase in the actual temperature.
0...2...15 K
Note
0...4...15 K
Note
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 135