KNX
Parameters
7.10.1.1
No
7.10.1.1.1
Dependent parameter
Max. manual increase in heating mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint increase that can be manually set via KNX in heating
mode. You can use the Request setpoint adjustment group object to increase the Comfort heating setpoint
by a maximum of the value set here.
If the object receives a value that exceeds the value set here, the maximum possible increase is applied,
and a request with the new temperature is sent via KNX in the Confirm setpoint adjustment group object.
7.10.1.1.2
Dependent parameter
Max. manual reduction in heating mode via KNX
This parameter is only displayed if you select No when setting Connect analog room control unit to
physical device input a.
Options:
The parameter determines the maximum setpoint reduction that can be manually set via KNX in Heating
mode. You can use the Request setpoint adjustment group object to increase the Comfort heating setpoint
by a maximum of the value set here.
If the object receives a value below the value set here, the maximum possible reduction is applied,
and a request with the new temperature is confirmed in the Confirm setpoint adjustment group object.
166 2CDC508220D0211 Rev. A | VC/S 4.x.1
0...3...9 K
Note
0...3...9 K
Note