ABB i-bus
KNX
Group objects
No.
14
This group object is enabled if the parameter Monitor receipt of group object "Dew point alarm" is set to Activated
in the Monitoring and safety parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the group object
being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
15
This group object is enabled if the parameter Monitor receipt of group object "Fill level alarm" is set to Activated
in the Monitoring and safety parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the group object
being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
16
This group object is enabled if the parameter Monitor receipt of group object "Operating mode" is set to Activated
in the Monitoring and safety parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the group object
being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
16
This group object is enabled if the parameter Monitor receipt of group object "Control value" parameter is set to Activated
in the Monitoring and safety parameter window. This parameter is only visible in the actuator mode.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the group object being
received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
Object function
Error: dew point alarm receipt
Error: fill level alarm receipt
Error: operating mode receipt
Error: control value receipt
Name
Channel A – General
Channel A – General
Channel A – General
Channel A – General
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 201
Data type
Flags
1 bit
C, R, T
DPT 1.002
1 bit
C, R, T
DPT 1.002
1 bit
C, R, T
DPT 1.002
1 bit
C, R, T
DPT 1.002