ABB i-bus
KNX
Group objects
8.5
Group objects Channel A – Input a
No.
27
This group object is enabled if the parameter Input is set to Temperature sensor in the Input a parameter window.
This group object sends the temperature value measured at the input on the bus depending on the reaction parametrized
in the parameter Send temperature value.
28
This group object is enabled if the parameter Input is set to Temperature sensor in the Input a parameter window.
This group object is also enabled if the parameter Connect analog room control unit to physical device input a is set to Yes
in the Setpoint adjustment parameter window.
This group object changes its status to 1 if a fault (idling or short circuit) is found at the input and it is therefore no longer
possible to send measured values.
If there is not fault at the input, this group object value is 0.
29
This group object is enabled if the parameter Input is set to Binary signal input in the Input a parameter window.
Depending on the selected parametrization, this group object indicates the contact position of the binary sensor connected to
the input.
29
This group object is enabled if the parameter Input is set to Window contact in the Input a parameter window.
Depending on the selected parametrization, this group object indicates the state of the window contact connected to the input.
29
This group object is enabled if the parameter Input is set to Dew point sensor in the Input a parameter window.
Depending on the selected parametrization, this group object indicates the state of the dew point sensor connected to the
input.
29
This group object is enabled if the parameter Input is set to Fill level sensor in the Input a parameter window.
Depending on the selected parametrization, this group object indicates the state of the fill level sensor connected to the input.
Object function
Temperature
Error: input
Switch
Window contact
Dew point alarm
Fill level alarm
Name
Channel A – Input a
Channel A – Input a
Channel A – Input a
Channel A – Input a
Channel A – Input a
Channel A – Input a
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 205
Data type
Flags
2 bytes
C, R, T
DPT 9.001
1 bit
C, R, T
DPT 1.002
1 bit
C, R, T
DPT 1.001
1 bit
C, R, T
DPT 1.019
1 bit
C, R, T
DPT 1.005
1 bit
C, R, W
DPT 1.005