Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.6.7.1.2.3
Dependent parameter
I-proportion
Options:
The standard value depends on the option selected in the Additional-stage heating parameter in the
Application parameters parameter window.
The I-proportion stands for the integral time in a control. The integral proportion causes the room
temperature to approach the setpoint slowly and also to reach it finally. Depending on the system type
used, the integral time may need to have different values. In principle the following applies: The more
sluggish the overall system, the larger the integral time is.
7.6.7.1.2.4
Dependent parameter
Extended settings
Options:
Extended settings can be enabled using this parameter. This parameter is displayed on the selection of
the Yes option.
Dependent parameter
Control value direction
This parameter is only visible if the Via group object option has been selected for the Actuate additional-
stage heating via parameter in the Application parameters parameter window.
Options:
This parameter is used to specify the control value direction if it is only output via a group object.
The setting is used to actuate NC (normally closed) or NO (normally opened) valves.
If one of the physical device outputs is used to output the control value, this parameter is not displayed
because this setting is then made in the related output stage.
Normal: The control value is output normally.
Control value On/100 % => telegram value On/100 %
Control value Off/0 % => telegram value Off/0 %
Inverted: The control value is output inverted.
Control value On/100% => telegram Off/0 %
Control value Off/0 % => telegram On/100%
0...100...255 min
No
Yes
Normal
Inverted
VC/S 4.x.1 | 2CDC508220D0211 Rev. A 93