ABB i-bus KNX Product Manual page 178

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.11.1.3.1
Dependent parameter
Fill level reached when
Options:
This parameter defines how the input reacts if the fill level is evaluated as reached or not reached.
You can also define whether the fill level sensor is a normally closed or normally open contact.
Contact open: The fill level is considered reached if the contact is open.
Contact closed: The fill level is considered reached if the contact is closed.
7.11.1.3.2
Dependent parameter
Send status value
Options:
After a change: Sends the value only after a change.
After a change and cyclically: Sends the value after a change, and cyclically. Enables the dependent
parameter Send input status cyclically.
176 2CDC508220D0211 Rev. A | VC/S 4.x.1
Contact open
Contact closed
After a change
After a change and cyclically