ABB i-bus KNX Product Manual page 84

Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Example:
Heating PWM cycle: 15 min
Control value: 33 %
Times
0 min
5 min
15 min
20 min
30 min
...
New control value: 0%
Times
60 min
75 min
90 min
...
New control value: 66 %
Times
120 min
130 min
135 min
145 min
...
82 2CDC508220D0211 Rev. A | VC/S 4.x.1
Sent value
1
0
1
0
1
...
Sent value
0
...
Sent value
1
0
1
0
...

Advertisement

Table of Contents
loading

Table of Contents