45.03 MOT TEMP ALM LIM
Defines the alarm limit for the motor overtemperature protection (when par.
=
(1) Alarm
or
(2)
0...200 °C
45.04 MOT TEMP FLT LIM
Defines the fault limit for the motor overtemperature protection (when par.
(2)
Fault).
0...200 °C
45.05 AMBIENT TEMP
Defines the ambient temperature for the thermal protection mode.
-60...100 °C
The temperature is supervised using a KTY84 sensor connected to
drive thermistor input TH.
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. Note: This selection
does not apply for FEN-01. *
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. Note: This selection
does not apply for FEN-01. *
The temperature is supervised using 1...3 PTC sensors connected to
drive thermistor input TH.
The temperature is supervised using 1...3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. *
The temperature is supervised using 1...3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. *
FW block:
MOT THERM PROT
Fault).
Motor overtemperature alarm limit.
FW block:
MOT THERM PROT
Motor overtemperature fault limit.
FW block:
MOT THERM PROT
Ambient temperature.
(2) KTY 1st FEN
(see above)
45.01 MOT TEMP PROT
(see above)
45.01
MOT TEMP PROT =