5.1.2 General device settings

For each EnOcean device, there is a list of general settings that can be configured to ease the
setup process. The list of available settings is listed in the KNX communication objects settings
part of the screen. Bellow, there is a list of all available parameters. Keep in mind that these
parameters will appear depending on the EnOcean device selected. Not all parameters are
available for all EnOcean devices.
a. Wait for data integrity before transmitting to EnOcean: When selected, no
data will be transmitted to the EnOcean interface until all data needed by the
device is received from the KNX interface.
b. EnOcean periodic output update: Indicates the period (in seconds) that the
existing values will be sent from the EnOcean part cyclically. It can be switched
off (disable) or set with following values: 30s, 1 min, 2 min, 5 min, 10 min, 20 min,
30 min or 40 min.
c. Edit initial data: Click on the link to pop-up a configuration window where default
or initial values can be set according to each EnOcean device. Check the link to
the EEP list to know exactly with type and range of values can be applied in each
case.
d. Hide controls of KNX periodic updates: When selected, KNX periodic input
update parameter for each communication object is not shown.
e. Contact: Indicates the functionality of the gateway when receiving messages
from the EnOcean device. Different options are:
i. Report last value reported by any device
ii. Report "Open" only when all devices report "Open"
iii. Report "Closed" only when all devices report "Closed"
f. Groupings: Used to select the working mode of the rocker buttons. For each
button and for each channel (pair of buttons) you have 4 different modes: none,
switching, dimming or shutter/blind. More information about these modes and the
associated DTP can be found in section 8.

5.1.3 Communication objects parameters

Depending on the communication object, certain parameters can be set up. Next, you have the
list of those available parameters grouped as integrated devices and simulated devices.
A. Integrated devices
Device
General
KNX periodic input update
Room
Minimum/Maximum
Operating
temperature setpoint
Panel
Switching operation:
Rocker
Short/long pulse threshold
Switch
Dimming operation for short
(long) pulse:
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
 +49 (0) 6221 701 724
EG/A 32.2.1
Parameter
Description
Indicates the period (in seconds) that the existing values will
be read from KNX cyclically.
(0= disabled; values from 10 to 2550, multiple of 10)
Indicates the maximum and minimum setpoint temperature
desired in the project.
(Expressed in ºC, range may vary depending on each device)
Functionality of the button when pressed.
(On, Off or Toggle)
Amount of time the button needs to be pressed to be
interpreted as a long pulse.
(Expressed in ms)
Functionality of the button when pressed and dimming mode is
selected.
(On (increase), Off (decrease) or Toggle)
www.abb.com/knx
Technische Helpline / Technical Support
 +49 (0) 6221 701 434 E-Mail: knx.helpline@de.abb.com
User's manual r1.5 eng
19 / 47