ABB i-bus KNX Product Manual page 36

Knx/enocean gateway
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®

i-bus
KNX
Status_ Fan Man/Auto
Status_ Fan Stage
Status_ Fan Stage Available
Status_ Normal /Hold-off Stop
Status_ Room Occupancy
Status_ Room Occupancy Frost
Status_ Room Occupancy Mode
PHC 1
Status_ Temperature
Status_ Control Variable
Status_ Controller Mode Off/Auto
Status_ Controller Cool/Heat
PHC 2
Status_ Controller Mode
Status_ Normal/Hold–off Stop
Status_ Room Occupancy
Status_ Room Occupancy Mode
Status_ Dimming Value
Status_ Ramping Time
PHC 3
Status_ Absolute/Relative Range
Status_ Store Final Value
Status_ Switching Command
PHC 4
Status_ Fan Stage
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
 +49 (0) 6221 701 724
EG/A 32.2.1
1 bit
DPT_Bool
1 byte
DPT_Scaling
1 bit
DPT_Bool
1 bit
DPT_Bool
1 bit
DPT_Occupancy
1 bit
DPT_Bool
1 byte
DPT_OccMode
2 bytes
DPT_Value_Temp
1 byte
DPT_Scaling
1 bit
DPT_Bool
1 bit
DPT_Bool
1 byte
DPT_ErrorClass_HVAC
1 bit
DPT_Bool
1 bit
DPT_Occupancy
1 byte
DPT_OccMode
1 byte
DPT_Scaling
2 bytes
DPT_Time_Periodic_Sec
1 bit
DPT_Bool
1 bit
DPT_Bool
1 bit
DPT_Switch
1 byte
DPT_Scaling
0 – Normal; 1 – Auto
1.002
R
T
5.001
R
T
%
0 – False; 1 – True
1.002
R
T
0 – Normal; 1 – Hold-off
1.002
R
T
0 – Not occupied; 1 – Occupied
1.018
R
T
0 – False; 1 – True
1.002
R
T
20.003
R
T
HVAC Control Mode
9.001
R
T
ºC
5.001
R
T
%
0 – Off; 1 – Auto
1.002
R
T
0 – Cooling; 1 – Heating
1.002
R
T
1 – Heat; 3 – Cool; 6 - Off
20.012
R
T
0 – False; 1 – True
1.002
R
T
0 – Not occupied; 1 – Occupied
1.018
R
T
20.003
R
T
HVAC Control Mode
5.001
R
T
%
7.005
R
T
Seconds
0 – Absolute; 1 – Relative
1.002
R
T
0 – False; 1 – True
1.002
R
T
0 – Off; 1 – On
1.001
R
T
5.001
R
T
%
www.abb.com/knx
Technische Helpline / Technical Support
 +49 (0) 6221 701 434 E-Mail: knx.helpline@de.abb.com