Fujitsu 2737 User Manual page 110

19-inch rack
Table of Contents

Advertisement

■ Measures against earthquakes
To have the rack system withstand earthquakes with an acceleration of more than 2.5 m/s
fix it in place with adequate earthquake-proofing measures. The earthquake-proofing measures
include using leveling feet and using the optional Quake Proof Stabilizer kit.
Warning
Use bolts to secure the rack to the floor (slab).
Failure to use bolts to secure the rack to the floor (slab) may cause the rack to fall
over during any earthquake with an acceleration of more than 2.5 m/s
If the rack falls over, the result may be severe injury and/or death. There may also be
damage to the devices in the rack and the surrounding area.
・ Quake Proof Stabilizer kit
Model
2724
2737
2742
2616
2624
2642
■ Securing the rack using the leveling feet
After the rack is transported to the installation site, install the rack so that it is anchored with the
leveling feet that are provided on the bottom of the rack. Adjust the leveling feet so that the rack is
level.
Keep the casters 1 to 2 mm above the floor.
'
110
Quake Proof Stabilizer kit type
For base rack
19R-27ST1
19R-26ST1
Casters
Rack
(top view)
Leveling
feet
(Front)
2
(250 gal).
For expansion rack
19R-27ST2
19R-26ST2
2
(250 gal),

Advertisement