6. 1. 3
Output a signal when reached to a specified
frequency (output the specified frequency
attainment signal)
<F101: Reach signal specified frequency>
<F102: Reach signal detection band>
■ Function
When the output frequency becomes the frequency that is equal to the value for <F101: Reach
signal specified frequency> plus or minus the value for <F102: Reach signal detection band>, the
ON signal (specified frequency attainment signal) is output from a specified output terminal.
■ Parameter setting
Title
Parameter name
F101
Reach signal specified
frequency
F102
Reach signal detection
band
<F101>
<F101>
Output terminal
(Specified frequency
attainment)
Terminal [F]
(Fwd run)
■ Output terminal parameter setting
When you want to output the specified frequency attainment signal to the output terminal [FP], set
"8" for <F130: Terminal FP function 1>.
When you want to output the signal from the relay logic output terminals [FLA]-[FLB]-[FLC], set
<F132: Terminal FL function>. When you want to output the signal from the [R1A]-[R1C] terminals,
set <F133: Terminal R1 function 1>. When you want to output the signal from the terminals [R2A]-
[R2C] set <F134: Terminal R2 function >.
0.0-FH
0.0-FH
Output frequency (Hz)
<F102>
<F101>
<F102>
0
6-5
STOP
F101 : Reach signal frequency
Min: 0.0
X1000
X100
Adjustment range
Time (s)
ON
OFF
ON
OFF
6. [Advanced] How to use parameters
E6582062
0.0Hz
12:45
0.0
Hz
Max: 80.0
X10
X1
Unit
Default setting
Hz
0.0
Hz
2.5
3
4
6
9