Setting Of Extended Parameters That Are Especially Important; Switching Two Frequency Commands - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

5. 3
Setting of extended parameters that are
especially important
This section explains the parameters that are especially important among the extended parameters.
For other extended parameters not introduced here, refer to "Chapter 6".
5. 3. 1

Switching two frequency commands

<FMOd: Frequency command select 1>
Basic parameter
<F207: Frequency command select 2>
<F200: Frequency command priority select>
<F208: Frequency command switching frequency>
■ Function
Two frequency commands, for example manual setting with external potentiometer and automatic
setting with 4 - 20 mA signals, can be switched.
Switch two frequency commands set with <FMOd: Frequency command select 1> and <F207:
Frequency command select 2> with input terminal signals or switching frequency set with <F200:
Frequency command priority select>.
Easy mode
5-65
STOP
0.0Hz
F200 : Fmod/F207 priority
0: FmOD/F207 (switched by TB)
1: FmOD/F207 (switched by F208)
STOP
0.0Hz
F208
:F200=1 switching frequency
0.1
Min: 0.1
Max: 80.0
X1000
X100
X10
5. [Fundamental operation] How to use parameters
E6582062
15:34
3
4
5
15:34
Hz
9
X1