Changing Frequency By The Terminal Up And Down Signal - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 6. 5
Changing frequency by the terminal UP and DOWN
signal
<F264: Terminal Up response time>
<F265: Terminal Up frequency step>
<F266: Terminal Down response time>
<F267: Terminal Down frequency step>
<F268: Initial Up/Down frequency>
<F269: Up/Down frequency rewrite>
■ Function
These parameters are the frequency commands that input the logic signals to the two input
terminals for the UP and DOWN signals. You can input a logic signal either as a continuous signal or
as a pulse signal.
Set <FMOd: Frequency command select 1>= "15".
■ Parameter setting
Title
Parameter name
F264
Terminal Up response
time
F265
Terminal Up frequency
step
F266
Terminal Down response
time
F267
Terminal Down frequency
step
F268
Initial Up/Down
frequency
F269
Up/Down frequency
rewrite
■ Input terminal parameter setting
Three input terminals are used.
Two of the three input terminals are used for the UP and DOWN signals. The other input terminal is
used for the signal that clears the set frequency command.
Input terminal function
88
Terminal Up frequency
90
Terminal Down frequency
92
Terminal Up, Down frequency clear
F264 : TB Up response time
Min: 0.0
X1000
Adjustment range
0.0-10.0
0.0-FH
0.0-10.0
0.0-FH
LL-UL
0: F268 is not changed.
1: F268 is changed after power off.
ON
Frequency setting increase
Frequency setting decrease
OFF → ON: Input terminal up/
down frequency command
clear
6-29
E6582062
STOP
0.0Hz
12:59
0.1
s
Max: 10.0
X100
X10
X1
Unit
Default setting
s
0.1
Hz
0.1
s
0.1
Hz
0.1
Hz
0.0
1
OFF
-
-
<F268> setting
6. [Advanced] How to use parameters
3
4
6
9