7
Commissioning
ange from one to two columns
During commissioning, the mechanical mounting on the linear
and part-turn actuators is checked. For this purpose, the
actuator is first moved into the end positions and Autoadjust is
then carried out.
7.1
Checks prior to commissioning
Air pressure in the compressed air connecting line:
1.4 ... 10 bar (20 ... 145 psi)
Current input active:
4 ... 20 mA
7.2
Checking mechanical mounting
7.2.1
Moving to end positions (Autoadjust already
performed)
Process display
1. Use
to switch to the operating modes menu.
Operating Mode
Auto Adjust
O
Adaptive
O
Control
O
Manual SP
O
Manual Sensor
Configuration
Back
2. Use
or
to select the "Manual Sensor" operating
mode.
OK
3. Use
and
to move to the relevant end position.
-45.0
Pos. Ang.
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
— between -30 ... 30° for linear actuators
— between -45 ... 45° for part-turn actuators
7.2.2
Moving to end positions (with new device)
Process display
Electronic
1. Use
and
to move to the relevant end position.
-45.0
Pos. Ang.
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
— between -30 ... 30° for linear actuators
— between -45 ... 45° for part-turn actuators
Autoadjust must then be performed. Please refer to the 8.2.3
"Start Auto Adjust function chapter for a description of how
Autoadjust is performed.
°
°