ABB PositionMaster EDP300 Operating Instruction page 51

Electro-pneumatic positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

No.
Error message
24
Insufficient supply
pressure
25
Overpressure from supply Supply air pressure too
26
Supply pressure limit low
exceeded
27
Supply pressure limit high
exceeded
28
Pressure hammer from
supply
30
Pressure Measurement
defect
33
Friction limit exceeded
34
Stiction limit exceeded
35
Universal Input out of
range
36
Partial Stroke failed
37
Option Module defect
38
Universal Input Limit
exceeded
39
Analog Output Simulation
active
40
Binary Output Simulation
active
41
Fail Safe Active - via
Device Error
42
Fail Safe Active - via User
43
Binary Input active
44
Switchpoint 1 exceeded
45
Switchpoint 2 exceeded
202
Mess1 Extern Access
203
Mess2 All Locked
204
Mess3 Conf. Locked
205
Mess5
Squawk
1
1
Function can only be used via HART7
Possible cause
Troubleshooting
Supply air pressure is too
Check supply air
low or filter is clogged
pressure or filter
Check supply air
high
pressure
Supply air pressure is too
Check supply air
low or filter is clogged
pressure or filter
Supply air pressure too
Check supply air
high
pressure
Supply air pressure too
Check supply air
high
pressure
Faulty pressure
Replace pressure option
measurement
Excessive dynamic
Service valve
friction
Excessive stiction
Service valve
Incorrectly scaled
Check parameter settings
universal input signal or
of universal input or
faulty universal input
universal input device
device
Friction is too high
Check valve
Defective option module
Replace option module
Universal input limit value
Depends on application
overshot
Faulty electronics
Replace electronics
Safety position activated
Switch off service mode
by the user
Digital input activated by
Deactivate the digital
the user
input
Valve has passed limit 1
Depends on application
position
Valve has passed limit 2
Depends on application
position
Communication with the
Depends on application
device is performed via
HART
Local operation is locked
Activate the digital input
Configuration is locked
Activate the digital input
"Find device" activated
Deactivate function in
DTM or EDD
X
X
X
X
X
X
X
X
X
X
X
X
PositionMaster EDP300 | OI/EDP300-EN 51
Alarm group
Operation
Operation
Operation
Operation
Operation
Electronics
X
Actuator
X
Actuator
Actuator
X
Actuator
X
Electronics
X
Actuator
Actuator
Electronics
X
Operation
X
Operation
x
Process
x
Process
Configuration
Configuration
Configuration
Configuration