Menu Levels - ABB PositionMaster EDP300 Operating Instruction

Electro-pneumatic positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

8.2

Menu levels

There are two levels under the process display.
Information level
Diagnostics
Operator Page 1
Signal View
Change from one to two columns
Process
The process display shows the current process values.
display
Information
The information level contains the parameters and
level
information that are relevant for the operator. The device
configuration cannot be changed on this level.
Operating
In the operating modes menu, the Autoadjust function
modes menu
can be started for commissioning purposes. You can
also change the operating modes and switch to the
configuration level.
Configuration
The configuration-, parameterization instruction contains
level
all the parameters required for device commissioning
and configuration. The device configuration can be
changed on this level.
Process display
Operating modes menu
Auto Adjust
Adaptive
Control
Manual SP
Manual Sensor
Configuration
Configuration level
Easy Setup
Device Setup
Display
Control
Input / Output
Communication
Diagnostics
Device Info
Service
NOTICE – Property damage!
During external configuration via a PC, the
positioner no longer responds to the setpoint
current. This may lead to process failures. Prior to
external configuration, always move the actuator
to the safety position and activate manual
adjustment.
IMPORTANT (NOTE)
For a detailed description of the individual
parameters and menus on the configuration level,
please refer to the 8.3 "Overview of parameters
on the configuration level" and 8.4 "Parameter
descriptions" chapters.