ABB PositionMaster EDP300 Operating Instruction page 41

Electro-pneumatic positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

Menu: DIGIT. FEEDBACK
... / .../ DIGIT. FEEDBACK
Mask contents
Value range
Switch 1
Switch 1 Funct.
Switch 1 Value
Switch 1 Logic
Switch 1 Activ.
SW 1 MASK MAP
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
Switch 1 Sim.
Switch 2
Switch 2 Funct.
Switch 2 Value
Switch 2 Logic
Switch 2 Activ.
SW 2 MASK MAP
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
Switch 2 Sim.
Menu: Digit. Feedback / Switch 1
... / .../ Digit. Feedback / Switch 1
Mask contents
Value range
Switch 1 Funct.
Position Info
Diagnostic state
Switch 1 Value
0 ... 100%
Switch 1 Logic
Active High
Active Low
Switch 1 Activ.
Fall Below
Exceeding
Description
The function of switch 1 is configured in this parameter group.
Switch 1 Funct. – Switch 1 function
Switch 1 Value – Switch 1 value
Switch 1 Logic – Switch 1 logic
Switch 1 Activ – Switch 1 activation.
The function of switch "1 MASK MAP" is configured in this parameter group.
SW 1 Mask Map – Switch 1 diagnostics assignment
Switch 1 Sim. – Switch 1 simulation
The function of switch 2 is configured in this parameter group.
Switch 2 Funct. – Switch 2 function
Switch 2 Value – Switch 2 value
Switch 2 Logic – Switch 2 logic
Switch 2 Activ – Switch 2 activation.
SW 2 Mask Map – Switch 2 diagnostics assignment
Switch 2 Sim. – Switch 2 simulation
The function of switch "2 MASK MAP" is configured in this parameter group.
SW 2 Mask Map – Switch 2 diagnostics assignment
Switch 2 Sim. – Switch 2 simulation
Description
Use this parameter to select whether the switch is to be used as a limit signal generator or for
signaling diagnostics messages.
Position Info – Evaluate position
Diagnostic State – Evaluate diagnostic state
Use this parameter to configure the position value as a limit signal generator. It is taken into
account when the "Switch 1 Funct." parameter is set to "Position Info".
Use this parameter to select the contact logic.
Active High (active) = Output current I > 2.1 mA
Active Low (active) = Output current I < 1.2 mA
Use this parameter to select the edge for activating the switch.
Fall Below – When undershooting
Exceeding – When exceeding
PositionMaster EDP300 | OI/EDP300-EN 41