Selection Of Operation Mode - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.2

Selection of operation mode

6.2.1 Selection of start/stop and frequency settings
cmod : Command mode selection
fmod : Frequency setting mode selection
 Function
These parameters are used to specify which input device (panel keypad, terminal block, or
communication) takes priority in entering an operation stop command or frequency setting mode (terminal
VIA/VIB/VIC, setting dial, communication, or UP/DOWN from external logic).
<Command mode selection>
[Parameter setting]
Title
Command mode selection

[Programmed value]
Terminal block
:
operation
Panel keypad
:
operation
RS485
:
communication
CANopen
3:
communication
Communication
4:
option
* Operation command selected by  and the operation commands from the terminal block can be
switched alternately with ON/ OFF of input terminal. (input terminal function number 108, 109) See the table of
input terminal function selection in section 11.6.
* When priority is given to commands from a linked computer or terminal block, they have priority over the
setting of .
Function
0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: CANopen communication
4: Communication option
ON and OFF of an external signal run and stop operation.
Press the
and
RUN
Operation can also be done from the extension panel.
Run/stop operations by RS485 communication from an external device.
 Refer to section 6.38.
Run/stop operations by CANopen communication from an external device.
 Refer to "CANopen communication Instruction Manual E6581911".
Run/stop operations by commands from a communication option.
 Refer to each Instruction Manual of option.
F-13
Adjustment range
keys on the panel keypad to run and stop.
STOP
E6582175
Default setting
1
6