2.3

Description of terminals

2.3.1
 Connections with peripheral equipment
Molded-case
circuit braker
2
Power
supply
Note 1: The T/L3 terminal is not provided for any single-phase models. So if you are using single-phase
 Power circuit
Terminal symbol
R/L1,S/L2,T/L3
U/T1,V/T2,W/T3
PA/+, PB
PA/+
PC/-
PO, PA/+
The arrangements of power circuit terminals are different from each range.
Refer to section 1.3.3.1) for details.
Power circuit terminals
Magnetic
Input AC
noise
contactor
reactor
reduction filter
models, use the R/L1 and S/L2/N terminals to connect power cables.
Grounding terminal for connecting inverter. There are 3 terminals in cooling fin or
mounting part of EMC plate.
240V class : Three-phase 200 to 240V-50/60Hz
: Single-phase 200 to 240V-50/60Hz
500V class : Three-phase 380 to 500V-50/60Hz
* Single-phase inputs are R/L1 and S/L2/N terminals.
Connect to three-phase motor.
Connect to braking resistors.
Change parameters , , ,  if necessary.
This is a positive potential terminal in the internal DC main circuit.
DC common power can be input between PA/- terminal and PC/- terminal.
This is a negative potential terminal in the internal DC main circuit.
DC common power can be input between PC/- terminal and PA/+ terminal.
Terminals for connecting a DC reactor (DCL: optional external device). Shorted by a
Shorting-bar when shipped from the factory. Before installing DCL, remove the
shorting-bar.
Inverter
U/T1
R/L1
S/L2
V/T2
W/T3
T/L3
PA/+
PB
Braking resistor
Terminal function
B-6
E6582175
Motor
M
Zero-phase
reactor