Toshiba Tosvert VF-S15 Instruction Manual page 158

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.11.2 Run/stop control with frequency command
f241 : Operation starting frequency
f242 : Operation starting frequency hysteresis
 Function
[Parameter setting]
Title
f241
f242
6
The Run/stop of operation can be controlled simply with frequency command.
Function
Operation starting frequency
Operation starting frequency hysteresis
Output frequency [Hz]
 
 +

 
 -

0
Adjustment range
0.0-fh (Hz)
0.0-fh (Hz)
When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
A
B
100% Frequency command value
F-46
E6582175
Default setting
0.0
0.0