 Setting of switching terminals
To switch to motor 2, assign the following functions to a terminal not being used. It is also possible to switch
to acceleration/deceleration 2 (AD2). Refer to section 6.27 for details.
It is possible to set 3 functions for terminal F and R, and 2 functions for terminal S1 and RES.
Input terminal function number
24
26
28
AD2
AD3
VF2
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
-
OFF
-
Note 1: Each of the following numbers (25, 27, 29, 33, 153) are reverse signals.
Note 2: pt and "V/F constant" cannot be switched while running. Stop the motor before switching.
When the motor is switched, wait for starting to drive for 0.2 seconds or more.
vl and f170, vlv and f171, vb and f172 can be switched while running.
Note 3: If motor is switched, the setting to retain and subtract an integral value of motor electronic thermal is possible.
Refer to section 5.6 for details.
 Example of setting a terminal for switching: Sink logic
F (F: Forward run)
S1(AD2)
S2(VF2)
S3(OCS2)
Parameters changed from applicable parameters and
32
152
default standards
OCS2
MOT2
Default setting :
OFF
OFF
acc→fs00, dec→f501, f502→fs03
OFF
OFF
acc→fs10, dec→f511, f502→fs12
OFF
OFF
During stop : pt→V/F constant, vl→f170,
vlv→f171, vb→f172, thr→f173
OFF
OFF
During run : vl→f170, vlv→f171,
vb→f172
f601 → f185
ON
OFF
→, →, → , →,
→( is fixed when =or),
-
ON
→,→, →,
→
Forward run command
CC
2nd acceleration/deceleration switch
2nd V/F setting switch
2nd stall prevention operation switch
F-35
E6582175
pt, vl, vlv, vb, thr,
acc, dec, fs02, f601