Siemens SIMATIC S7-1200 Function Manual page 326

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Instructions
9.2 PID_3Step
Tag
CtrlParamsBackUp.Gain
CtrlParamsBackUp.Ti
CtrlParamsBackUp.Td
CtrlParamsBackUp.TdFiltRatio REAL
CtrlParamsBack-
Up.PWeighting
CtrlParamsBack-
Up.DWeighting
CtrlParamsBackUp.Cycle
CtrlParamsBack-
Up.InputDeadBand
PIDSelf-
Tune.SUT.CalculateParams
PIDSelfTune.SUT.TuneRule
PIDSelfTune.SUT.State
326
Data type Default
REAL
1.0
REAL
20.0
REAL
0.0
0.2
REAL
1.0
REAL
1.0
REAL
1.0
REAL
0.0
BOOL
FALSE
INT
1
INT
0
Description
Saved proportional gain
Saved integration time in seconds
Saved derivative action time in seconds
Saved derivative delay coefficient
Saved proportional action weighting
Saved derivative action weighting
Saved sampling time of PID algorithm in seconds
Saved dead band width of the control deviation
The properties of the controlled system are saved during
tuning. If CalculateParams = TRUE, the PID parameters are
recalculated on the basis of these properties. The PID pa-
rameters are calculated using the method set in TuneRule.
CalculateParams is set to FALSE following calculation.
Methods used to calculate parameters during pretuning:
SUT.TuneRule = 0: PID fast I
SUT.TuneRule = 1: PID slow I
SUT.TuneRule = 2: Chien, Hrones and Reswick PID
SUT.TuneRule = 3: Chien, Hrones, Reswick PI
SUT.TuneRule = 4: PID fast II
SUT.TuneRule = 5: PID slow II
The SUT.State tag indicates the current phase of pretuning:
State = 0: Initialize pretuning
State = 50: Determine start position without position
feedback
State = 100: Calculate the standard deviation
State = 200: Find the point of inflection
State = 300: Determine the rise time
State = 9900: Pretuning successful
State = 1: Pretuning not successful
Function Manual, 03/2017, A5E35300227-AC