Pid_Temp Errorbits Parameter - Siemens SIMATIC S7-1200 Function Manual

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

9.3.4.8

PID_Temp ErrorBits parameter

If several errors are pending simultaneously, the values of the ErrorBits are displayed with
binary addition. The display of ErrorBits = 0000003h, for example, indicates that the errors
0000001h and 0000002h are pending simultaneously.
ErrorBits
Description

 ( DW#16#...)
0000000
There is no error.
0000001
The "Input" parameter is outside the process value limits.
Input > Config.InputUpperLimit or
Input < Config.InputLowerLimit
If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_Temp
remains in automatic mode.
If manual mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_Temp
remains in manual mode.
If pretuning or fine tuning mode was active before the error occurred and ActivateRecoverMode =
TRUE, PID_Temp switches to the operating mode that is saved in the Mode parameter.
0000002
Invalid value at "Input_PER" parameter. Check whether an error is pending at the analog input.
If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_Temp
outputs the configured substitute output value. As soon as the error is no longer pending, PID_Temp
switches back to automatic mode.
If manual mode was active before the error occurred and ActivateRecoverMode = TRUE, PID_Temp
remains in manual mode.
If pretuning or fine tuning mode was active before the error occurred and ActivateRecoverMode =
TRUE, PID_Temp switches to the operating mode that is saved in the Mode parameter.
0000004
Error during fine tuning. Oscillation of the process value could not be maintained.
If PID_Temp is used as heating-cooling controller (Config.ActivateCooling = TRUE), to be able to gen-
erate actual value oscillation, the PID output value (PidOutputSum) at the setpoint must be
positive for fine tuning heating
negative for fine tuning cooling
If this requirement is not met, use the tuning offsets ( PIDSelfTune.TIR.OutputOffsetCool and PIDSelf-
Tune.TIR.OutputOffsetHeat tags), see Fine tuning (Page 185).
If ActivateRecoverMode was = TRUE before the error occurred, PID_Temp cancels the tuning and
switches to the operating mode that is saved in the Mode parameter.
0000008
Error at start of pretuning. The process value is too close to the setpoint or greater than the setpoint.
Start fine tuning.
If ActivateRecoverMode = TRUE before the error occurred, PID_Temp cancels the tuning and switches
to the operating mode that is saved in the Mode parameter.
0000010
The setpoint was changed during tuning.
You can set the permitted fluctuation of the setpoint at the CancelTuningLevel tag.
If ActivateRecoverMode = TRUE before the error occurred, PID_Temp cancels the tuning and switches
to the operating mode that is saved in the Mode parameter.
0000020
Pretuning is not permitted during fine tuning.
If ActivateRecoverMode = TRUE before the error occurred, PID_Temp remains in fine tuning mode.
0000040
Error during pretuning. Cooling could not reduce the process value.
If ActivateRecoverMode = TRUE before the error occurred, PID_Temp cancels the tuning and switches
to the operating mode that is saved in the Mode parameter.
PID control
Function Manual, 03/2017, A5E35300227-AC
Instructions
9.3 PID_Temp
439