9.3 PID_Temp
Reaction to error
The behavior in the case of an error is determined by the tags SetSubstituteOutput and
ActivateRecoverMode. If ActivateRecoverMode = TRUE, the behavior also depends on the
error that occurred.
SetSubstitute-
Acti-
Output
vateRecov-
erMode
Not relevant
FALSE
FALSE
TRUE
TRUE
TRUE
In manual mode, PID_Temp uses ManualValue as output value, unless ManualValue is
invalid.
● If ManualValue is invalid, SubstituteOutput is used.
● If ManualValue and SubstituteOutput are invalid, Config.Output.Heat.PidLowerLimit is
used.
The Error parameter indicates if an error is pending. When the error is no longer pending,
Error = FALSE. The ErrorBits parameter shows which errors have occurred. ErrorBits is
reset by a rising edge at Reset or ErrorAck.
382
Configuration editor
> Basic settings of output
> Set PidOutputSum to
Zero (inactive)
Current value for error while error is
pending
Substitute output value while error
is pending
Reaction
Switch to "Inactive" (State = 0) mode
The output value of the PID algorithm and all
outputs for heating and cooling are set to 0. The
scaling of the outputs for heating and cooling is
not active.
Switch to "Substitute output value with error moni-
toring" mode (State = 5)
The current output value is transferred to the
actuator while the error is pending.
Switch to "Substitute output value with error moni-
toring" mode (State = 5)
The value at SubstituteOutput is transferred to the
actuator while the error is pending.
Function Manual, 03/2017, A5E35300227-AC