Output parameters TCONT_CP

Table 9- 20
Output parameters TCONT_CP
Parameter
Address
PV
14.0
LMN
18.0
LMN_PER
22.0
QPULSE
24.0
QLMN_HLM
24.1
QLMN_LLM
24.2
QC_ACT
24.3
See also
Operating principle of the pulse generator (Page 481)
Block diagram TCONT_CP (Page 484)
Parameter STATUS_H (Page 494)
Parameters STATUS_D (Page 495)
PID control
Function Manual, 03/2017, A5E35300227-AC
Data
Default
Description
type
REAL
0.0
The effective process value is output at the "Process value" output.
The valid values depend on the sensors used.
REAL
0.0
The effective "Manipulated value" is output in 
 f loating point format at the
"Manipulated 
 v alue" output.
INT
0
The manipulated value in I/O format is interconnected with the controller
on the output "Manipulated value I/O".
BOOL
FALSE
The manipulated value is pulse-width-modulated at the QPULSE output.
BOOL
FALSE
The manipulated value is always restricted to a high limit and low limit.
The output QLMN_HLM signals that the high limit has been reached.
BOOL
FALSE
The manipulated value is always restricted to a high limit and low limit.
The output QLMN_LLM signals that the low limit has been reached.
BOOL
TRUE
This parameter indicates whether continuous control component will be
processed the next time the block is called (relevant only when SELECT
has the value 0 or 1).