Using PID_Compact
4.2 PID_Compact V2
Example
PID_Compact sampling time = 100 ms
PID algorithm sampling time = 1000 ms
Minimum ON time = 200 ms
Output is a constant 15%. The smallest pulse that PID_Compact can output is 20%. In the
first cycle, no pulse is output. In the second cycle, the pulse not output in the first cycle is
added to the pulse of the second cycle.
①
②
⑤
In order to minimize operation frequency and conserve the actuator, extend the minimum ON
and OFF times.
If you are using "Output" or "Output_PER", you must configure the value 0.0 for the minimum
ON and OFF times.
Note
The minimum ON and OFF times only affect the output parameter Output_PWM and are not
used for any pulse generators integrated in the CPU.
80
PID_Compact sampling time
PID algorithm sampling time
Minimum ON time
Function Manual, 03/2017, A5E35300227-AC
PID control