Fault Descriptions And Corrective Measures - Siemens SIMATIC S7-1200 Function Manual

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

7.3.3.6

Fault descriptions and corrective measures

Compensating operator errors
Operator error
TUN_ON and setpoint step
change or TUN_ST are set sim-
ultaneously
Effective TUN_DLMN < 5% (end
of phase 1)
Point of inflection not reached (only if excited by setpoint step change)
At the latest, tuning is ended when the process value has passed 75% of the setpoint step
change (SP_INT-PV0). This is signaled by "inflection point not reached" in STATUS_H
(2xx2x).
The currently valid setpoint always applies. By reducing the setpoint, it is possible to achieve
an earlier end of the tuning function.
In typical temperature processes, cancelation of tuning at 75% of the setpoint step change is
normally adequate to prevent overshoot. However, caution is advised, particularly in
processes with a greater delay (TU/TA > 0.1, process type III). If manipulated variable
excitation is too strong compared to the setpoint step change, the process value can
overshoot heavily (up to a factor of 3).
In higher-order processes, if the point of inflection is still a long way off after reaching 75% of
the setpoint step change, there will be significant overshoot. In addition, the controller
parameters are too stringent. In this case, you should reduce the controller parameters or
repeat the attempt.
PID control
Function Manual, 03/2017, A5E35300227-AC
STATUS and action
Transition to phase 1; how-
ever, tuning is not started.
SP_INT = SP
or
old
TUN_ST = FALSE
STATUS_H = 30002
Transition to phase 0
TUN_ON = FALSE
SP = SP
old
Using PID basic functions
7.3 TCONT_CP
Comment
The setpoint change is canceled.
This prevents the controller from
settling to the new setpoint value
and from leaving the stationary
operating point unnecessarily.
Tuning is canceled.
The setpoint change is canceled.
This prevents the controller from
settling to the new setpoint value
and from leaving the stationary
operating point unnecessarily.
231

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500

Table of Contents