Advanced Videographic Recorder
SM2000
D.2.8 QSDAIRY
As D.2.5 QSRTD_C except:
Recording
Primary sample rate
Chart View
Screen interval
Bargraph View
Bargraph view enable
Archiving
Archive file enables
Alarm event log file
Audit log file
New file interval
Recording Channel Setup
Source indentifiers
Channel 1.1
Channel 1.2
All other channels
Analog Input A1
Engineering range
Low
High
Units
Short tag
Long tag
Broken sensor direction
Analog Input A2
Engineering range
Low
High
Units
Short tag
Long tag
Broken sensor direction
IM/SM2000
Issue 11
1 min
2 days/screen
Off
True
True
Daily
Analog input A1
Analog input A2
None
–10.0
90.0
°C
Tank
Tank Temperature
Upscale
–10.0
90.0
°C
Return
Return Temperature
Upscale
Ch1.1 Alarm A
Alarm type
Trip
Hysteresis/Delay time
Hysteresis
Delay time
Enable source
Log enable
Ch1.1 Alarm B
Alarm type
Trip
Hysteresis/Delay time
Hysteresis
Delay time
Enable source
Log enable
Relay modules
Source
Relay C1
Relay C2
Relay C3
Polarity
Logic equations
Logic equation 1
All other logic equations
1 Applicable only if the Advanced Math and Logic option is
enabled.
Appendix D – Default Settings
Delayed high process
10.0 °C
0.5 °C
7200 Secs
Digital I/P C1
On
Delayed high process
12.0 °C
0.5 °C
1200 Secs
Digital I/P C2
On
Logic equation 1
None
None
+ve
Alarm state 1.1B and
Digital I/P C1 or Alarm
state 1.1A
Off
127