Digital Input Configuration - ABB SM2000 User Manual

Advanced videographic recorder
Hide thumbs Also See for SM2000:
Table of Contents

Advertisement

Advanced Videographic Recorder
SM2000

4.6.3 Digital Input Configuration

Note. The 'Digital I/P' tab is displayed only if 'Source ID' for the Recording Channel is set to a digital signal source – see
Section 4.6.1, page 77.
•1 If this parameter is changed, internally recorded data files are recreated and unarchived data is lost.
IM/SM2000
Issue 11
•1
Note. This parameter is displayed only if 'Input type' on the
'Analog I/P' tab is set to 'Volt free digital input'. If this parameter
is changed to anything other than 'Volt free digital input', the
input channel reverts to an analog input channel – see
Section 4.6.2, page 80.
Enter the tag to be displayed on channel indicators when the
•1
digital signal is active (6 characters max.).
Note. Tags with a high percentage of capital letters and wide
characters such as 'W' or 'M' may appear truncated in some
Operator views. In such cases, use lower case letters or fewer
characters.
Enter the tag to be displayed on channel indicators when the
•1
digital signal is inactive (6 characters max.).
Enter the tag name to be displayed on channel indicators and
used to identify the channel in archive files (8 characters max.).
Note. Tags with a high percentage of capital letters and wide
characters such as 'W' or 'M' may appear truncated in some
Operator views. In such cases, use lower case letters or fewer
characters.
Enter the tag name to be displayed in the Process view and
used in the archive files (20 characters max.).
4 CONFIGURATION
83

Advertisement

Table of Contents
loading

Table of Contents