10.3.3.3

X524 electronics power supply

Table 10- 21 X524 electronics power supply
5-pin socket,
max. connectable cross-section: 4 x 0.75 mm
Note
The maximum cable length for the P24 supply of the DME20 is 100 m.
In case no UL-compliant design is required, is the use of the following cables and connectors
from Siemens is recommended:
Pre-assembled cables
Connecting cable for power supply with M12 plug and M12 socket,
A-coded, 4-pin,
order number: 6XV1801-5D..
Cables to be assembled by the user
Cable
24 V DC cable,
2-wire, 2 x 0.75 mm
order number: 6XV1812-8A
Table 10- 22 Cable length P24 supply cable
connected
1
loads
1)
Cross section
0.34 mm²
75 m
2 x 0.34 mm²
100 m
0.75 mm²
100 m
2 x 0.75 mm²
100 m
T
= 55 °C
a
100 m DRIVE-CLiQ
1) Connected motors with DRIVE-CLiQ encoder, DRIVE CLiQ mounted encoder SME
SINAMICS S120 Combi
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3
Pin
Designation
1
Electronics power supply
2
Electronics power supply
3
Electronics ground
4
Electronics ground
5
not connected
2
,
2
2
45 m
90 m
100 m
100 m
10.3 DRIVE-CLiQ Hub Module External DME20
Technical specifications
The connection voltage of 20.4 V – 28.8 V refers
to the (terminal) voltage at the DME20. This
must be taken into account when selecting the
cable cross-section and supply cable lengths.
Pins 1 and 2: jumpered internally
Pins 3 and 4: jumpered internally
Connector
M12 plug connector,
4-pin, A-coded,
order number: 6GK1907-0DC10-6AA3
3
4
30 m
25 m
65 m
50 m
75 m
60 m
100 m
100 m
Additional system components
5
20 m
40 m
50 m
100 m