S120 Combi Power Modules
3.3 Interface description
3.3.4

X11 brake connection

Table 3- 7
Brake connection X11
Terminal
BR +
BR -
Connector
Only protective extra-low voltages (PELV) must be connected to all connections and
terminals between 0 and 48 V DC.
The voltage tolerances of the motor holding brakes (24 V ± 10%) must be taken into
account.
Note
The motor brake must be connected via connector X11. The BR- cable must not be
connected directly to electronics ground (M).
3.3.5

X12/X13 fan connection

Table 3- 8
X12/X13 connection of the external fan unit
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Type: Screw terminal 1 (see Chapter "Control cabinet installation and EMC / connection system")
70
Designation
Brake connection +
Brake connection -
WARNING
Designation
Ground
Fan monitoring
+24 V
Ground
2
Technical specifications
Voltage 24 V DC
max. load current 1 A
min. load current 0.1 A
Max. connectable cross-section 2.5 mm
Type: Spring-loaded terminal 1 (see Chapter "Control
cabinet installation and EMC / connection system")
The brake connector is part of the prefabricated cable.
Technical specifications
Current-carrying capacity, 2 x 1 A or 1 x 2 A
Manual, Edition 07/2012, 6SL3097-4AV00-0BP3