9.2

G(P).RIRD

The G(P).RIRD instruction reads the specified points of data from the buffer memory or the device in the CPU module
of the target station.
[Instruction
[Execution
symbol]
condition]
G.RIRD
GP.RIRD
Setting
Internal device
data
(System, user)
Bit
Word
(S)
(D1)
(D2)
(1) Setting data
*1
Device
Start I/O number of the module (First two digits of I/O number written
Un
with three digits)
(S)
Start number of the device in which control data is stored
(D1)
Start number of the device to which read data is stored
Device that turns on for one scan upon completion of reading.
(D2)
(D2) + 1 also turns on at an abnormal end.
*1
The local device and the file register of each program cannot be used as a device for setting data.
Command
Command
Applicable device
Link direct
device
File
J\
register
Bit
Word
Description
CHAPTER 9 DEDICATED INSTRUCTIONS
G.RIRD
Un
(S)
GP.RIRD
Un
(S)
Intelligent
function module
Index
device
register Z
U\G
Setting range
0 to FE
Within the range of the
specified device
Within the range of the
specified device
Within the range of the
specified device
(D1)
(D2)
(D1)
(D2)
Constant
Others
K, H
$
Data type
16-bit binary
H
Device name
Bit