Maximum output frequency
With SINAMICS G150 cabinet units, the maximum output frequency is limited to 100 Hz or 160 Hz due to the factory-
set pulse frequency of f
Pulse
clock cycle = 250 μs). The pulse frequency must be increased if higher output frequencies are to be achieved. Since
the switching losses in the motor-side IGBT inverter increase when the pulse frequency is raised, the output current
must be reduced accordingly.
Permissible output current and maximum output frequency as a function of pulse frequency
The table below states the rated output currents of SINAMICS G150 converters with the factory-set pulse frequency,
as well as the current derating factors (permissible output currents referred to the rated output current) at higher
pulse frequencies.
The pulse frequencies for the values in the orange boxes can be selected simply by changing a parameter (even
during operation), i.e. they do not necessitate a change to the factory-set current controller clock cycle. The pulse
frequencies for the values in the grey boxes require a change in the factory-set current controller clock cycle and can
therefore be selected only at the commissioning stage. The assignment between current controller clock cycles and
possible pulse frequencies can be found in the List Manual (Parameter List).
Under certain boundary conditions (line voltage at low end of permissible wide-voltage range, low ambient
temperature, restricted speed range), it is possible to partially or completely avoid current derating at pulse
frequencies which are twice as high as the factory setting. Further details can be found in section "Operation of
converters at increased pulse frequency".
Rated output current
Output power
current derating factor
at
with pulse frequency of
400 V / 500 V / 690 V
1.25 kHz
380 V – 480 V 3AC
110 kW
132 kW
160 kW
200 kW
250 kW
315 kW
605 A
400 kW
745 A
450 kW
840 A
560 kW
985 A
630 kW
1120 A
710 kW
1380 A
900 kW
1560 A
500 V – 600 V 3AC
110 kW
175 A
132 kW
215 A
160 kW
260 A
200 kW
330 A
250 kW
410 A
315 kW
465 A
400 kW
575 A
500 kW
735 A
560 kW
810 A
630 kW
860 A
710 kW
1070 A
1000 kW
1360 A
1)
G150 parallel connection / the specified currents represent the total current of all inverter sections
SINAMICS G150: Permissible output current (current derating factor) as a function of pulse frequency
SINAMICS Engineering Manual – November 2015
304/528
Ó Siemens AG
= 1.25 kHz (current controller clock cycle = 400 μs) or f
or
2.0 kHz
2.5 kHz
210 A
95 %
260 A
95 %
310 A
97 %
380 A
96 %
490 A
94 %
83 %
72 %
83 %
72 %
87 %
79 %
92 %
87 %
1)
83 %
72 %
1)
83 %
72 %
1)
87 %
79 %
92 %
87 %
92 %
87 %
92 %
88 %
89 %
82 %
89 %
82 %
92 %
87 %
91 %
85 %
87 %
79 %
83 %
72 %
1)
92 %
87 %
1)
91 %
85 %
1)
87 %
79 %
= 2.00 kHz (current controller
Pulse
Current derating factor
with pulse frequency of
4.0 kHz
5.0 kHz
82 %
74 %
83 %
74 %
88 %
78 %
87 %
77 %
78 %
71 %
64 %
60 %
64 %
60 %
64 %
55 %
70 %
60 %
64 %
60 %
64 %
60 %
64 %
55 %
70 %
60 %
70 %
60 %
71 %
60 %
65 %
55 %
65 %
55 %
67 %
55 %
64 %
50 %
64 %
55 %
61 %
55 %
67 %
55 %
64 %
50 %
64 %
55 %
7.5 kHz
8.0 kHz
54 %
50 %
54 %
50 %
54 %
50 %
54 %
50 %
53 %
50 %
40 %
40 %
40 %
50 %
40 %
40 %
40 %
40 %
40 %
40 %
40 %
35 %
35 %
35 %
25 %
35 %
35 %
35 %
25 %