1.14.2.3 Partial load efficiency of S120 Smart Line Modules

The chart below shows the partial-load efficiency of air-cooled SINAMICS S120 Smart Line Modules.The calculations
are based on a typical efficiency at full load of 98.5 %. The efficiency is represented as a function of the active output
power ratio P
/P
supplied to the connected SINAMICS S120 Motor Modules by the SLM or drawn from the
Out
Out-100
connected SINAMICS S120 Motor Modules by the SLM and regenerated to the mains supply.
Efficiency of air-cooled S120 Smart Line Modules as a
function of the active output power ratio P

1.14.2.4 Partial load efficiency of S120 Active Line Modules + Active Interface Modules

The chart below shows the partial-load efficiency of air-cooled and liquid-cooled SINAMICS S120 Active Line
Modules including the assigned air-cooled Active Interface Modules. The calculations are based on typical efficiency
values at full load. These are 98.5 % with Active Line Modules and 99 % with the assigned Active Interface Modules,
corresponding to a total efficiency η
output power ratio P
/P
Out
Out-100
from the connected SINAMICS S120 Motor Modules by the ALM+AIM and regenerated to the mains supply.
Efficiency of air-cooled and liquid-cooled S120 Active Line Modules including the assigned
air-cooled Active Interface Modules as a function of the active output power ratio P
Fundamental Principles and System Description
/P
in %
Out
Out-100
= 97.5 %. The efficiency is represented as a function of the active
100-(ALM+AIM)
supplied to the connected SINAMICS S120 Motor Modules by the ALM+AIM or drawn
SINAMICS Engineering Manual – November 2015
Engineering Information
/P
in %
Out
Out-100
Ó Siemens AG
185/528