Maximum Power Rating Of Drive Configurations At A Common Dc Busbar - Siemens SINAMICS G130 Engineering Manual

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Motor Modules 380 V to 480 V 3AC
Power
Frame size
[ kW ]
110
FX / FXL
132
FX / FXL
160
GX / GXL
200
GX
250
GX / GXL
315
HX / HXL
400
HX / HXL
450
HX / HXL
560
JX / JXL
710
JX
800
JX / JXL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Contribution of individual S120 Motor Modules to the total short-circuit current on the DC busbar
To dimension the DC busbar, it is first of all necessary to calculate the normal operating currents and to select the
cross-sections of the DC busbar accordingly. The total peak short-circuit current which could potentially develop in
the event of a short circuit must then be calculated. Finaly it must be verified that the selected DC busbar can
withstand the calculated peak short-circuit current. For further information about the peak short-circuit currents
permitted for the DC busbars of SINAMICS S120 Cabinet Modules, please refer to section "Required DC busbar
cross-sections and maximum short-circuit currents" in chapter "General Information about Modular Cabinet Units
SINAMICS S120 Cabinet Modules".
1.8.2.5

Maximum power rating of drive configurations at a common DC busbar

Within the scope of the SINAMICS S120 modular drive system, it is possible to build drive configurations in which a
S120 Infeed (Basic Infeed, Smart Infeed or Active Infeed) comprising one or up to four parallel-connected S120 Line
Modules supplies a DC busbar with several S120 Motor Modules. With a line voltage of 690 V, therefore, up to 6 MW
of power (4 • 1500 kW) can be fed into the busbar. The DC busbar current reaches values of up to 7500 A. The
busbar itself can extend to up to 30 m or more in length depending on the ratings of the Motor Modules and the
number of other components which might be connected (e.g. Braking Modules, dv/dt filters or output-side switches).
The system of modular, type-tested SINAMICS S120 built-in units in Chassis format and the associated system
components are capable of supplying up to 6 MW of infeed power (4 • 1500 kW) to the DC busbar with a line voltage
of 690 V, provided that the cabinet builder has dimensioned the drive configuration properly in terms of its electrical,
thermal and mechanical properties.
Adequate fuse protection for the drive configuration must be provided on the line side. The power cables and bars,
especially the DC busbar, must be dimensioned with sufficient thermal and mechanical strength to tackle with short
circuits in the system. Furthermore, to cope with ground faults in the system, PE bars must be properly dimensioned
and connections of sufficient low resistance must be provided between the S120 Chassis and the relevant cabinet
frames and between individual cabinet frames in the drive configuration. To ensure sufficient cooling, the required
flow of cooling air must be provided using air ventilation holes of adequate cross-section and using partitions for
adequate air guidance. To ensure fault-free operation, especially in large configurations of high-power drives, EMC-
compliant cable routing and shield connections must be implemented. Therefore it is absolutely essential to take care
of the following rules:
·
Provide the recommended line-side protection in form of fuses or circuit breakers, and ensure that the circuit
breakers are correctly set for the relevant plant conditions.
·
Observe the permissible short-circuit currents of the DC busbar.
·
Provide the recommended protection for Motor Modules connected to the DC busbar.
·
Comply with the required cross-sections for supply system connection, DC busbar and motor connection.
·
Comply with the recommended length and topology of the DC busbar.
·
Comply with the required ventilation hole cross-sections and the recommended partitioning for air-guidance.
·
Provide adequate air conditioning of the electrical equipment room (cooling capacity, volumetric flow).
·
Comply with the EMC installation guideline.
Fundamental Principles and System Description
Motor Modules 500 V to 690 V 3AC
Peak short-circuit current
[ kA ]
1.8
2.2
2.7
3.3
4.2
5.3
6.7
7.5
9.4
11.9
13.4
-
-
-
-
-
-
-
SINAMICS Engineering Manual – November 2015
Engineering Information
Power
Frame size
[ kW ]
75
FX
90
FX / FXL
110
FX
132
FX / FXL
160
GX
200
GX / GXL
250
GX
315
GX / GXL
400
HX
450
HX / HXL
560
HX / HXL
710
JX / JXL
800
HXL
800
JX / JXL
900
JX
1000
JX / JXL
1200
JX / JXL
1500
JXL
Ó Siemens AG
Peak short-circuit current
[ kA ]
1.4
1.6
2.0
2.4
2.9
3.6
4.5
5.7
7.2
8.1
10.1
12.8
14.4
14.4
16.2
18.0
21.6
27.0
129/528

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents