8.3 Factory settings (defaults) of customer interface on SINAMICS S150 with TM31

A PROFIBUS interface is provided as standard on the CU320-2 DP Control Unit. This is exchanged for a PROFINET
interface when the CU320-2 PN Control Unit is used (option K95).
The customer terminal block on the TM31 Terminal Module (option G60) can be used optionally. This interface allows
the S150 converter to be linked to the higher-level control by means of digital and analog signals, and also permits
the connection of additional devices.
The optional customer terminal block on the TM31 Terminal Module (option G60) includes:
· 8 digital inputs (DI)
· 4 bidirectional inputs/outputs (DI/DO)
· 2 analog inputs (differential) (AI)
· 2 analog outputs (AO)
· 2 relay outputs (changeover contact) (DO)
· 1 input for KTY84 or PT1000 temperature sensor or PTC thermistor (Temp)
· Auxiliary voltage output ±10 V for analog setpoint input
· Auxiliary voltage output +24 V for digital inputs
[1]
Drive ON/OFF1
[2]
Increase setpoint /
fixed setpoint bit 0
[3]
Decrease setpoint /
fixed setpoint bit 1
[4]
Acknowledge fault
[5]
Enable inverter
[6]
Freely parameterizable as
digital input
[7]
Freely parameterizable as
digital input
[8]
Freely parameterizable as
digital input
[9]
Analog input for setting
speed setpoint
[10] Analog input (reserved)
[11] Analog output, actual
speed value
[12] Analog output, actual
motor current value
[13] Connection option for a
KTY84 or PT1000
temperature sensor or
PTC thermistor
[14] Ready (factory default
setting as digital output)
[15], [16], [17]
Freely parameterizable as
digital inputs / outputs
(assigned as digital inputs
with factory setting)
[18] Checkback signal
"Inverter enable"
[19] Checkback signal "No
converter fault"
Optional customer terminal block on the TM31 Terminal Module (option G60)
1)
Jumpers must be inserted for this circuit example (M: Internal ground, M1 or M2: External ground)
2)
Parameterizable as current or voltage source
3)
Individually parameterizable as digital input/output (factory setting: Assigned as output)
SINAMICS Engineering Manual – November 2015