Dv/Dt Filters Plus Vpl; Sine-Wave Filters; Maximum Connectable Motor Cable Lengths - Siemens SINAMICS G130 Engineering Manual

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

8.8.2

dv/dt filters plus VPL

The dv/dt filter plus VPL (option L10) and the dv/dt filter compact plus VPL (option L07) comprise two components,
the dv/dt reactor and the voltage limiting network (Voltage Peak Limiter), which limits voltage peaks and returns the
energy back to the DC link.
The dv/dt filter plus VPL and the dv/dt filter compact plus VPL must be used when the dielectric strength of the
insulation system on the motor to be connected is unknown or inadequate. Siemens standard and trans-standard
asynchronous motors generally require a filter (depending on the motor range) only with line supply voltages of
> 460 V or > 500 V in cases where no special insulation is provided on the motor side. Further information can be
found in chapter "Motors".
The dv/dt filter plus VPL limits the voltage rate-of-rise to values < 500 V/µs and the typical voltage spikes at the motor
to the values below:
·
V
(typically) < 1000 V
PP
·
V
(typically) < 1250 V
PP
The dv/dt filter compact plus VPL limits the voltage rate-of-rise to values of < 1600 V/ms and the typical voltage spikes
on the motor to the following values:
·
V
(typically) < 1150 V
PP
·
V
(typically) < 1400 V
PP
For a more detailed description, please refer to section "dv/dt filters plus VPL and dv/dt filters compact plus VPL" in
chapter "Fundamental Principles and System Description".
8.8.3

Sine-wave filters

Sine-wave filters (option L15) are LC low-pass filters and constitute the most sophisticated filter solution. They are
significantly more effective than dv/dt filters in reducing the voltage rates-of-rise dv/dt and peak voltages V
operation with sine-wave filters imposes substantial restrictions in terms of the possible pulse frequency settings and
voltage and current utilization of the motor-side inverter (voltage and current derating).
For a more detailed description and for the derating data, please refer to the section "Sine-wave filters" of the chapter
"Fundamental Principles and System Description".
8.8.4

Maximum connectable motor cable lengths

The table below shows the maximum connectable motor cable lengths. The values apply to the motor cable types
recommended in the tables as well as to all other types of motor cable.
SINAMICS S150
Line supply voltage
Rated power at
Without reactor or filter
380 V – 480 V 3AC
110 kW -
500 V – 690 V 3AC
With one motor reactor (option L08)
380 V – 480 V 3AC
110 kW - 800 kW
500 V – 690 V 3AC
With dv/dt filter plus VPL (option L10)
380 V – 480 V 3AC
110 kW -
500 V – 690 V 3AC
With dv/dt filter compact plus VPL (option L07)
380 V – 480 V 3AC
110 kW -
500 V – 690 V 3AC
With sine-wave filter (option L15)
380 V – 480 V 3AC
110 kW - 250 kW
500 V – 690 V 3AC
110 kW - 132 kW
Permissible motor cable lengths for SINAMICS S150
for
V
Line
for
660 V < V
Line
for
V
Line
for
660 V < V
Line
400 V / 690 V
e.g. Protodur NYCWY
800 kW
75 kW - 1200 kW
75 kW - 1200 kW
800 kW
75 kW - 1200 kW
800 kW
75 kW - 1200 kW
< 575 V
< 690 V
< 575 V
< 690 V
Maximum permissible motor cable length
Shielded cable
300 m
300 m
300 m
300 m
300 m
300 m
100 m
100 m
300 m
300 m
SINAMICS Engineering Manual – November 2015
SINAMICS S150
Engineering Information
Unshielded cable
e.g. Protodur NYY
450 m
450 m
450 m
450 m
450 m
450 m
150 m
150 m
450 m
450 m