6.3 Rated data, permissible output currents, maximum output frequencies

6.3.1

Permissible output currents and maximum output frequencies

With SINAMICS S120 Motor Modules, the maximum output frequency is limited to about 100 Hz or about 160 Hz due
to the factory-set pulse frequency in vector control mode (vector-type drive object) of f
controller clock cycle = 400 μs) or f
be increased if higher output frequencies are to be achieved. Since the switching losses in the motor-side inverter
increase when the pulse frequency is raised, the output current must be reduced accordingly.
Permissible output current and maximum output frequency as a function of pulse frequency
The table below states the rated output currents of SINAMICS S120 Motor Modules in Chassis format with the factory-set
pulse frequency, as well as the current derating factors at higher pulse frequencies (permissible output currents referred to
the rated output current). The table applies both to air-cooled and liquid-cooled units. In addition to the output power of the
relevant Motor Module, the first column also states the Chassis frame size(s) for which the current derating factors are valid.
The pulse frequencies for the values in the orange boxes can be selected simply by changing a parameter (even
during operation), i.e. they do not necessitate a change to the factory-set current controller clock cycle. The pulse
frequencies for the values in the grey boxes require a change in the factory-set current controller clock cycle and can
therefore be selected only at the commissioning stage. The assignment between current controller clock cycles and
possible pulse frequencies can be found in the List Manual (Parameter List).
Rated output current
Output power
at
current derating factor
400 V / 690 V
with pulse frequency of
Frame size / output
1.25 kHz
3AC 380 V – 480 V
FX / FXL
110 kW
FX / FXL
132 kW
GX / GXL
160 kW
GX
200 kW
GX / GXL
250 kW
605 A
HX / HXL
315 kW
HX / HXL
400 kW
745 A
HX / HXL
450 kW
840 A
985 A
JX / JXL
560 kW
1260 A
JX / JXL
710 kW
JX / JXL
800 kW
1405 A
JX / JXL
800 kW
3AC 500 V – 690 V
FX
75 kW
85 A
100 A
FX / FXL
90 kW
FX
110 kW
120 A
FX / FXL
132 kW
150 A
175 A
GX
160 kW
GX / GXL
200 kW
215 A
GX
250 kW
260 A
330 A
GX / GXL
315 kW
HX
400 kW
410 A
HX / HXL
450 kW
465 A
575 A
HX / HXL
560 kW
HXL
710 kW
735 A
JX
710 kW
735 A
1
)
810 A
HXL
800 kW
JX / JXL
800 kW
810 A
JX
900 kW
910 A
1025 A
JX / JXL
1000 kW
JX / JXL
1200 kW
1270 A
JXL
1500 kW
1560 A
1) The 800 kW liquid-cooled Motor Module in frame size HXL should only be operated at the factory-set pulse frequency of 1.25 kHz. Where higher
pulse frequencies are required, the 800 kW liquid-cooled Motor Module in frame size JXL should be used because to the better current derating factors
SINAMICS S120: Permissible output current (current derating factor) as a function of pulse frequency
SINAMICS Engineering Manual – November 2015
348/528
Ó Siemens AG
= 2.00 kHz (current controller clock cycle = 250 μ). The pulse frequency must
Pulse
or
2.0 kHz
2.5 kHz
210 A
95 %
260 A
95 %
310 A
97 %
380 A
96 %
490 A
94 %
83 %
72 %
83 %
72 %
87 %
79 %
92 %
87 %
92 %
87 %
-
1330 A
88 %
97 %
95 %
93 %
89 %
92 %
88 %
92 %
88 %
90 %
84 %
92 %
87 %
92 %
87 %
92 %
88 %
89 %
82 %
89 %
82 %
92 %
87 %
91 %
85 %
84 %
74 %
87 %
79 %
82 %
71 %
97 %
95 %
92 %
87 %
91 %
86 %
87 %
79 %
87 %
79 %
Current derating factor
with pulse frequency of
4.0 kHz
5.0 kHz
82 %
74 %
83 %
74 %
88 %
78 %
87 %
77 %
78 %
71 %
64 %
60 %
64 %
60 %
64 %
55 %
70 %
60 %
70 %
60 %
55 %
-
74 %
60 %
71 %
60 %
71 %
60 %
71 %
60 %
66 %
55 %
70 %
60 %
70 %
60 %
71 %
60 %
65 %
55 %
65 %
55 %
67 %
55 %
64 %
50 %
53 %
40 %
64 %
55 %
52 %
40 %
71 %
55 %
67 %
55 %
64 %
50 %
55 %
40 %
55 %
40 %
= 1.25 kHz (current
Pulse
7.5 kHz
8.0 kHz
54 %
50 %
54 %
50 %
54 %
50 %
54 %
50 %
53 %
50 %
40 %
40 %
40 %
50 %
50 %
-
50 %
40 %
40 %
40 %
35 %
40 %
40 %
40 %
40 %
35 %
35 %
35 %
25 %
25 %
25 %
35 %
33 %
30 %
25 %
25 %