I 2 T Cb Wear; Output Matrix Test; Siemens Protection Devices Limited - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR210 & 7SR220 Description of Operation
Binary outputs can be mapped to each of the above counters, these outputs are energised when the user
defined Count Target or Alarm Limit is reached.
The above counters can be triggered and reset from a binary input or command.
6.2.1
2
I
t CB Wear
2
An I
t counter is also included; this can provide an estimation of contact wear and maintenance requirements. The
algorithm works on a per phase basis, measuring the arcing current during faults. The I
is added to the previously stored value and an alarm is given when any one of the three phase running counts
exceeds the set Alarm limit. The (t) value is the time between CB contacts separation when an arc is formed,
Separation Time, and the CB Clearance time.
The I
2
t value can also triggered and reset from a binary input or command.
6.2.2

Output Matrix Test

The feature is only visible from the Relay fascia and allows the user to operate the relays functions. The test of
the function will automatically operate any Binary Inputs or LED's already assigned to that function. Any protection
function which is enabled in the setting menu will appear in the Output Matrix Test.
Unrestricted Page 88 of 94
2
t value at the time of trip
©2018 Siemens Protection Devices Limited

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents