Virtual Input/Outputs; Self Monitoring; Figure 2.11-1 Start-Up Counter Meter; Figure 2.11-2 Start-Up Counter Meter - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.10 Virtual Input/Outputs

The relays have 16 virtual input/outputs, these are internal logic states. Virtual I/O is assigned in the same way as
physical Binary Inputs and Binary Outputs. Virtual I/O is mapped from within the INPUT CONFIG > INPUT
MATRIX and OUTPUT CONFIG > OUTPUT MATRIX menus.
The status of the virtual inputs and outputs is volatile i.e. not stored during power loss.

2.11 Self Monitoring

The relay incorporates a number of self-monitoring features. Each of these features can initiate a controlled reset
recovery sequence.
Supervision includes a power supply watchdog, code execution watchdog, memory checks by checksum and
processor/ADC health checks. When all checks indicate the relay is operating correctly the 'Protection Healthy'
LED is illuminated.
If an internal failure is detected, a message will be displayed. The relay will reset in an attempt to rectify the
failure. This will result in de-energisation of any binary output mapped to 'protection healthy' and flashing of the
protection healthy LED. If a successful reset is achieved by the relay the LED and output contact will revert back
to normal operational mode, and the relay will restart, therefore ensuring the circuit is protected for the maximum
time.
A Start-up Counter Meter is provided to display the number of start-ups the relay has performed. Once the
number of start-ups has exceeded a set number, an Alarm output can be given.
Reset of the counter can be done from the meter or via a binary input or a command.
Various types of start-up are monitored by the relay:
1. power-on starts (auxiliary supply initiation)
2. expected starts (user initiated via comms, language changes, custom protection curve etc.)
3. unexpected starts (caused by the relay watchdog)
Any combination of these can be selected for the start-up count. This is done in the MAINTENANCE
MENU>START COUNT menu using the Start Up Types setting. All the start-up types selected will be added to
the overall start-up count.
The number of restarts before the alarm output is raised is set in the MAINTENANCE MENU>START COUNT
menu using the Start Up Count Target setting.
When the number of relay start-ups reaches the target value an output is raised, OUTPUT MATRIX>Start Up
Count Alarm, which can be programmed to any combination of binary outputs, LED's or virtual outputs.
As a further safeguard, if the Relay performs a number of unexpected starts SYSTEM CONFIG>Unexpected
Restart Count in a given time SYSTEM CONFIG>Unexpected Restart Period, it can be configured using the
SYSTEM CONFIG>Unexpected Restart Blocking setting to remove itself from service. In this case the Relay
will display a typical error message such as: -
Unrestricted ©2018 Siemens Protection Devices Limited

Figure 2.11-1 Start-up Counter Meter

Figure 2.11-2 Start-up Counter Meter

7SR210 & 7SR220 Description of Operation
Page 23 of 94

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents